Description
VPIS for M.V. cubicles (switchgear)
DXN series of voltage presence indicating system (VPIS) indicates the voltage presence on M.V. cubicles by being installed on the capacitive dividers.
Product Features
- 3-phase live-voltage indicating system
- Can work with phase comparator for phase checking
- Have the function of overvoltage protection
- Maximum loading current: 50A
- With self-locking terminals (self-locking force > 5KG)
- Wide-range 3kV- 40.5kV
- Working frequency 50/60Hz
- Threshold values for voltage presence indication: U>0.45 x Unmin
- Threshold values for voltage absence indication: U<0.10 x Unmax
- Threshold values for over-voltage protection: <0.30 x Unmin
- Divider capacitance 18pF or be specified by buyer
- Temperature range -25°C to +40°C
- Insulation strength: AC 2kV, 1min
- Product dimensions (W×H×D) 130x28x52mm
Technical Parameter
Executive Standard | IEC61958-2000 |
Working Frequency | 50Hz/60Hz |
Nominal Voltage | 3-6kV |
6-12kV | |
10-24kV | |
24-40.5kV | |
Divider Capacitance | 18pF, or customized by buyers |
Threshold Values for Voltage Presence Indication | U>0.45 x Unmin |
Threshold Values for Voltage Absence Indication | U<0.10 x Unmax |
Threshold Values for Over-voltage Protection | U<0.30 x Unmin |
Working Temperature | -25℃ – +40℃ |
Working Humidity | <95% |
Insulation Strength | 2kV,1min |
Protection Level | IP20 |
Overall Dimension (WxHxD) | 130x28x52 mm |
Mounting Dimension (WxHxD) | 105x22x48.5 mm (The distance between two screw holes is 120 mm) |
Shielded Cable Length | Type A: L1=960mm; L2=1070mm; L3=1180mm, or customized by buyers |