Short Circuit and Earth Fault Indicator EKL7

Description

(for 3kV-40.5kV Power Distribution Networks)

—EKL7

Short Circuit and Earth Fault Indicator indicates high voltage power line short circuit fault by detecting the 3 single-phase line-currents and short circuit currents, and the grounding fault by detecting the zero sequence currents. With visual or audible indicators, it helps line patrol staff to fast find out the location where there is a short circuit or grounding fault on the 3kV-40.5kV power distribution networks, switchgears or cable branching units etc.

Short circuit fault alarm indication

Short-circuit fault sensors installed on 3 single phase cables, monitoring the current changes of the power supply lines, when the current change value reaches or exceeds Threshold currents for short circuit alarm (this value can be set as per user requirement), the short circuit fault sensors output alarm signal, through optical fiber the signal will be sent to the indicator host, the corresponding fault indicator light will flash to alarm the short circuit fault.

 

Earth fault alarm indication

Earth fault sensor installed on the bifurcation unshielded part of three-phase cable, detection the zero sequence current value of the three-phase cable, when its value reaches or exceeds the threshold currents for grounding fault alarm (this value can be set as per user’s requirement), the earth fault sensor outputs alarm signal, through optical fiber the signal will be sent to the indicator host, the earth fault indicator light will flash to alarm the earth fault.

 

Product Features

  • Short-circuit and earth fault detection with 3 single-phase current sensors, and one grounding current sensor
  • Short-circuit indication (3 single phase L1,L2,L3) by three super bright LEDs respectively
  • Threshold current for short circuit alarm can be set at the options of 400A, 600A, 800A ,1000A and it also can be automatically adjustable according to the load current
  • Alarm response time for short circuit can be set at the options of 40ms, 60ms, 80ms and 100ms
  • Earth fault indication by one super bright LED display
  • Threshold current for earth fault can be set at the options of 20A, 40A, 60A and 80A
  • Alarm response time for earth fault can be set at the options of 80ms, 120ms, 160ms and 200ms
  • Remote indication via 2 relay contacts
  • Auxiliary power supply: 24V-230V DC/AC or built-in Li-ion battery with low-power-status indication
  • Self check
  • Reset/Test Button
  • Remote reset
  • Reset: auto-reset: 1h/2h/4h/8h reset time for options or manual reset by “RESET” button

 

Technical Data

Model number EKL7
Voltage level 3kV-40.5kV
Ambient temperature  -25°C to +70°C
humidity ≤95%
 Threshold currents for short circuit alarm can be set or be adjustable at the options of 400A,600A, 800A and 1000A.
Alarm response time for short circuit 40ms, 60ms, 80ms, 100ms (optional)
 Threshold currents for grounding fault alarm 20A, 40A, 60A, 80A(optional)
Alarm response time for earth fault 80ms,120ms,160ms,200ms(optional)
alarm current accuracy ±10%
reset auto reset 1h, 2h, 4h, 8h
manual reset by “RESET” button
remote reset AC/DC 12-60V or AC/DC 110-230V
auxiliary power supply built-in battery Li-ion 3.6v2.25Ah
external 24V-230V DC/AC
working current stand by ≤5uA
indication alarm ≤0.8mA
capacity of relay contact 2A 30VDC/1A 125VAC
applicable conductor diameter short circuit sensor type A Φ20mm~Φ40mm
type B Φ30mm~Φ50mm
type C Φ50mm~Φ70mm
grounding sensor type A Φ60mm~Φ100mm
type C Φ80mm~Φ130mm
protection class indicator IP40
sensor IP65
fiber cable length for short circuit sensor  1.5m can be customized
fiber cable length for grounding sensor  2.5m can be customized
panel window size (WxH) 92x45mm
indicator size (WxHxD) 96X48x69mm
sensor size (WxHxD) 40x44x27mm

 

Product Dimensions

Terminal Diagram

Terminal Definitions

 

No. Marks Definitions
1  Fault Remote Relay Common contact of fault signal remote transmission relay
2 Normally-closed contact of fault signal remote transmission relay
3 Normally-open contact of fault signal remote transmission relay
4 Low Power Relay Common contact of low battery signal remote transmission relay
5 Normally-closed contact of low battery signal remote transmission relay
6 Normally-open contact of low battery signal remote transmission relay
7 Remote Reset Remote reset terminal
8
9 Blinking Lamp White cable terminal of external alarm device
10 Brown cable terminal of external alarm device
11 CT Brown Brown cable terminal of short circuit sensor for the Phase L1
12 White White cable terminal of short circuit sensor for the Phase L1
13 CT Brown Brown cable terminal of short circuit sensor for the Phase L2
14 White White cable terminal of short circuit sensor for the Phase L2
15 CT Brown Brown cable terminal of short circuit sensor for the Phase L3
16 White White cable terminal of short circuit sensor for the Phase L3
17 CT Brown Brown cable terminal of earth fault sensor
18 White White cable terminal of earth fault sensor

 